This puts forward several requirements for the installation of exhaust pipes for Weifang generator sets, with specific content introduced by Huaquan Power.
Design of smoke exhaust pipeline
1. A soft connection should be installed between the smoke pipe and the Weifang generator set to absorb the thermal expansion and contraction of the pipeline, the displacement and vibration of the unit, and reduce the heavy pressure of the smoke pipe on the unit and between the smoke pipes; Soft connections should be located as close as possible to the exhaust outlet of the unit (turbocharger or exhaust manifold).
2. It is recommended that Weifang power generation units do not share exhaust pipes with furnaces, boilers, or other equipment. The accumulation of carbon dust and condensate emitted by equipment during operation can cause damage to non operating units, and the lack of lubrication in passive driven boosters can lead to bearing failures.
3. The smoke exhaust pipe terminal should be equipped with rainproof caps, coverings, and other rainproof designs to prevent snow from entering. The smoke pipe near the unit should be equipped with a condensate collector and a drain valve.
4. The exhaust pipe should be well supported and fixed.
5. Unsupported noise reduction should not be installed at the unit manifold or unit boost outlet.
The positioning of exhaust outlets for Weifang generator sets: Convenient outlets are not suitable locations. Designers should consider wind direction, building design, layout, distance, and important fresh air inlets (windows, doors, air inlets, fresh air inlets for unit combustion, cooling ventilation inlets for unit cooling, etc.) to prevent fresh air from being polluted by exhaust; It is also necessary to reduce the impact of chimney noise on workers and neighbors, as well as the accumulation of dust contained in smoke exhaust on adjacent buildings.
The length of the smoke exhaust pipe: shorten the length of the smoke exhaust system as much as possible to reduce the system's resistance (back pressure); Facilitating smoke emissions; Reduce the chance of gas condensation and decrease the degree of flue gas.
Unit smoke exhaust system limitation: Minimize the pressure value of the smoke exhaust system as much as possible. Excessive pressure values can negatively affect combustion efficiency, increase exhaust temperature, resulting in engine power loss and shortened working life. Therefore, the length of the smoke pipe should be shortened as much as possible, the number of bends should be reduced, the silencing resistance should be reduced, and the diameter of the smoke pipe should be increased.
When installing the exhaust pipe of the Weifang generator set, principles should be followed to reduce diesel engine failures caused by the exhaust pipe. I hope the above introduction can provide users with reference.